Check the safety of your installations using the C.A 6454 loop tester
Innovative and particularly user-friendly, the C.A 6454 loop tester is particularly easy to use and offers enhanced metrological performance for testing installations' compliance with European and international standards: NF C 15-100, IEEE, VDE 0100, NIN/NIV, OVE EN-1, etc.
- direct, safe connection to installation mains
- reliable measurements due to automatic permutation of L and N inputs if conductors are reversed at socket connection
- automatic installation voltage and frequency measurement
- loop resistance and impedance: L-N, L-L,and L-PE from 0.20 to 4kΩ
- power-on ground measurement: earth loop and 1P earth with choice of measurement current (high for precision measurements or low so as not to trigger differential devices)
- short-circuit current displayed up to 40kA by calculation (Uref/ZL-PE)
- clamp measurement of current and leakage current (option)
- Cat. III, 600V
- programmable alarms, date-stamped recording of measurement readings, data printout using standard printer, direct transfer of data to PC (data transfer application included as standard)
- large backlit display / "hands-free" pouch
- battery operated - battery life: 2,000 tests
- dimensions: 270x250x180mm ; weight : 900g